Products

PANELS:-

 

Fabricated of prefabricated panels of 60 m. m. to 100 m. m. thickness minimum, modular complete with floor & ceiling panels, mounted on a flat, concrete base. Cold room is reliable under all condition for stored materials. Panels are fire resistant and self-extinguishing. Panels are Metal Sheet of 0.5 m. m thickness or non-corrosive metallic panels. Jointing of panels by tongue groove cam locks only and no riveting between walls and ceiling panels. Insulation material polyurethane foam core bounded to steel panels or extruded. Puff density will be 40 kg/m3

W.I.C floor is above 3” from the room ground level. WIC room floor will be either prefabricated floor panels, similar to wall panels & to be attached with wall panels with cam locks or concrete slabs to be provided in floor with insulation material in bottom like PUF & tar felt & wall panels to be anchored by drive pins to floor.

 

CONSTRUCTION :

This unit has double walled insulated PUF modular panels, which can easily be assembled at site without any major hassles. Stainless steel (SS-304 grade) inside and Pre-painted G.I. Finish out side

The unit has double walled leak proof metal door with lock, with a provision of opening door from inside. Forced air circulation for uniform temperature.

TEMPERATURE:-

WIC will maintain a internal temperature of +2°C to + 8°C adjustable according to ambient temperature.

It will have hold over time of 4-6 hrs.

INTELLIGENT CONTROL SYSTEM :

The controlling system having is PLC Base and PC communication on Ethernet
DOOR:-

a Door with heavy duty lock with internal safely release.

 

b FRP flush type doors with reputed accessories.

c Plastic curtain on doorways

d Door to be lockable with 100% fail safe provision for opening from inside.

e Door shall have an incandescent vapor proof light mounted on the interior of the door section.

f Easily opening and closing of door.

 

SENESOR:
Temperature sensor PT-100 used for measurement. Temp. In degree Celsius with 0.1°C.

COOLING SYSTEM:
Consist of hermitically sealed compressor coupled with evaporation coil and condenser, safe guarded by time delay circuit. CFC free refrigerant. The cooling system is made up of split type so as one can place the compressor coupled with condenser coil (Condenser unit) in well-ventilated area and avoid hot air throw in the stability room.

REFRIGERATION SYSTEM:-

a.Dual refrigeration system(100% stand by) air cooler refrigeration units.

b Automatic defrosting NON- CFC free refrigerant friendly.

c Unit suitable for ambient temp. up to 45oC

d Wall mounted 7 days temperature recording circular chart.

e Thermometer (Digital) display in front with remote sensor.

f Condenser unit consists compressor, oil separator, filters/dryers, stop valves, high and low pressure oil site glass, solenoid valves and other essential components.

g. Compressor will be of reputed make like Copeland, Danfoss, Kirloskar etc. and capacity will be almost 20,000 BTU to get the desire result compressor is capable to with stand voltage

fluctuation of ±10% of rated value. The compressor is auto cut after attaining the set temp.

h Split type system comprising of company fitted condensing unit, fan coil units and electrical panels, ready to installed

i It will not have 40 DBA at 1 Meter.

j Two identical compressor system, which should work

alternatively as per time programmer


ALARM:-

a. High/low temperature alarm.

b Should be audible.

c When there is power failure

d When door is left open

SHELVING:-

The room will be equipped with cantilevered shelving to three walls

Each shelf will be slotted to allow good air floor around the material stored.

The shelves will be capable of holding an evenly spread 70 kg load.

Shelf will be made from non-corrosive medical grade stainless steel.

Shelves will be approx 600 m.m wide.

 

SAFETY:
The unit is provided with safety devices for temperature under shoot in case of malfunction.

Stainless steel (SS-304 grade) inside and Pre-painted G.I. Finish out side

 

The unit works on 230 Volts AC and 50Hz mains supply.

 

Common Software: Chambers are connected on TCP/IP (Ethernet) with the centralized work station and transferring data in database. This centralized workstation provides the tool for viewing, trending and alarm management of chambers.

 

Temperature Scanner: 8 point scanner for temperature having 8 temperature probes provided with alarms to monitor various parts of equipment.

 

Stand by Cooling System (Auto Switch Over): A fully functional cooling system can be provided as standby. It comes in operation automatically when the regular system fails to function.

 

Door Access System with Touch Screen Display: The door access system restricts access to the chamber to authorized persons only. In this system a physical lock is provided additional to this password access control is provided. Maximum six users can access the chamber.

 

Remote Alarm System: Alarm for Temperature & Humidity deviations. Indicator LED to identify equipment deviation. Alarm hooter test push button

 

Mobile Alert System Suitable for Equipments whenever the alarm is generated by the system the user has to acknowledge the alarm with in predetermined time. If the user fails to acknowledge the alarm will send as a sums to 6 predefined numbers

Salient Features:-

  • CFC free refrigerants used,
  • Micro-processor based electronic control panel board,
  • Power Panel with necessary accessories,
  • Defrost controls available for Negative Temperature Units